USER'S INSTRUCTIONS: The project work you are about to view is on "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" . Please, sit back and study the below research material carefully. This project topic "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" have complete 5(five) Chapters. The complete Project Material/writeup include: Abstract + Introduction + etc + Literature Review + methodology + etc + Conclusion + Recommendation + References/Bibliography.Our aim of providing this "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" project research material is to reduce the stress of moving from one school library to another all in the name of searching for "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" research materials. We are not encouraging any form of plagiarism. This service is legal because, all institutions permit their students to read previous projects, books, articles or papers while developing their own works.
TITLE PAGE
BY
---
--/H2013/01430
DEPARTMENT OF ----
SCHOOL OF ---
INSTITUTE OF ---
APPROVAL PAGE
This is to certify that the research work, "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" by ---, Reg. No. --/H2007/01430 submitted in partial fulfillment of the requirement award of a Higher National Diploma on --- has been approved.
By
--- . ---
Supervisor Head of Department.
Signature………………. Signature……………….
……………………………….
---
External Invigilator
DEDICATION
This project is dedicated to Almighty God for his protection, kindness, strength over my life throughout the period and also to my --- for his financial support and moral care towards me.Also to my mentor --- for her academic advice she often gives to me. May Almighty God shield them from the peril of this world and bless their entire endeavour Amen.
ACKNOWLEDGEMENT
The successful completion of this project work could not have been a reality without the encouragement of my --- and other people. My immensely appreciation goes to my humble and able supervisor mr. --- for his kindness in supervising this project.
My warmest gratitude goes to my parents for their moral, spiritual and financial support throughout my study in this institution.
My appreciation goes to some of my lecturers among whom are Mr. ---, and Dr. ---. I also recognize the support of some of the staff of --- among whom are: The General Manager, Deputy General manager, the internal Auditor Mr. --- and the ---. Finally, my appreciation goes to my elder sister ---, my lovely friends mercy ---, ---, --- and many others who were quite helpful.
PROJECT DESCRIPTION: This work "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" research material is a complete and well researched project material strictly for academic purposes, which has been approved by different Lecturers from different higher institutions. We made Preliminary pages, Abstract and Chapter one of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" visible for everyone, then the complete material on "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" is to be ordered for. Happy viewing!!!
The project presents here is on design and construct a three phase auto-transformer of rating 5kva, and step down voltage of 415 and secondary taps of 0v, 180v, 200v, 230v and 240v. A three phase autotransformer is a special type of electrical transformer in which a common winding is shared by both high voltage & low voltage sides. Here, three phases AC is provided along the primary side and the output is collected from the secondary side. Actually, three phase auto transformers are used for such applications where small voltage corrections are required in the distribution system. Also, they are frequently used as an economical alternative of three phase distribution transformers to adjust the bus bar voltage with specific load requirements, when load isolation from the main line is not required.
CHAPTER ONE
1.0 INTRODUCTION
A transformer which has only one winding per phase part of which is common to both primary and secondary circuits. A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed to "step-up" or "step-down" voltages and works on the magnetic induction principle. A transformer has no moving parts and is a completely static solid state device, which insures, under normal operating conditions, a long and trouble-free life. It consists, in its simplest form, of two or more coils of insulated wire wound on a laminated steel core. When voltage is introduced to one coil, called the primary, it magnetizes the iron core. A voltage is then induced in the other coil, called secondary or output coil. The change of voltage (or voltage ratio) between the primary and secondary depends on the turns ratio of the two coils.
Using an auto-transformer is an economical and compact means of connecting electrical equipment to a power supply or a different voltage. Part of the winding is common to both primary and secondary circuits so there is no isolation between the two. This may be acceptable on some power transformer. Typical applications include motor loads of industrial machinery, electric heating, air conditioners. Performs same function as an isolation transformer of same KVA and voltage rating without the isolation feature. May be used in either step-up or step-down configuration. All terminals are clearly identified and easy to connect. Transformer terminations rated below 330A are supplied with suitable hardware and lugs for cable connection. Terminations above 330A are supplied with termination pads.
Generally quieter than the equivalent isolation transformers. May be used in either step-up or step-down configuration. Low regulation (typically less than 3%).
1.1 PURPOSE OF THE PROJECT
The purpose of this study is to design and construct a three phase auto-transformer of rating 5kva, and step down voltage of 415 and secondary taps of 0v, 180v, 200v, 230v and 240v that can be used for such applications where small voltage corrections are required in the distribution system.
1.2 SIGNIFICANCE OF THE PROJECT
The purpose of an auto transformer will be one of two things. The auto transformer can increase the voltage a bit. The auto transformer can also decrease the voltage by a bit if that is what is needed.
Three phase auto-transformers are frequently used in power applications to interconnect systems operating at different voltage levels, such as to 66 kV to 138 kV transmission line.
1.3 STATEMENT OF PROBLEM
An autotransformer does not provide electrical isolation between its windings as an ordinary transformer does; if the neutral side of the input is not at ground voltage, the neutral side of the output will not be either. A failure of the insulation of the windings of an autotransformer can result in full input voltage applied to the output. Also, a break in the part of the winding that is used as both primary and secondary will result in the transformer acting as an inductor in series with the load (which under light load conditions may result in near full input voltage being applied to the output). These are important safety considerations when deciding to use an autotransformer in a given application.
Because it requires both fewer windings and a smaller core, an autotransformer for power applications is typically lighter and less costly than a two-winding transformer, up to a voltage ratio of about 3:1; beyond that range, a two-winding transformer is usually more economical.
In three phase power transmission applications, autotransformers have the limitations of not suppressing harmonic currents and as acting as another source of ground fault currents. A large three-phase autotransformer may have a "buried" delta winding, not connected to the outside of the tank, to absorb some harmonic currents.
In practice, losses mean that both standard transformers and autotransformers are not perfectly reversible; one designed for stepping down a voltage will deliver slightly less voltage than required if it is used to step up. The difference is usually slight enough to allow reversal where the actual voltage level is not critical.
Like multiple-winding transformers, autotransformers use time-varying magnetic fields to transfer power. They require alternating currents to operate properly and will not function on direct current.
1.3 APPLICATIONS OF PROJECT
- Used in both Synchronous motors and induction motors.
- Used in electrical apparatus testing labs since the voltage can be smoothly and continuously varied.
- They find application as boosters in AC feeders to increase the voltage levels.
Used in HV Substation due to following reasons:
- If we use normal transformer the size of transformer will be very high which leads to heavy weight, more copper and high cost.
- The tertiary winding used in Autotransformer balances single phase unbalanced loads connected to secondary and it does not pass on these unbalanced currents to Primary side. Hence Harmonics and voltage unbalance are eliminated.
- Tertiary winding in the Autotransformer balances amp turns so that Autotransformer achieves magnetic separation like two winding transformers.
1.4 LIMITATION OF THE PROJECT
One of the limitations of the autotransformer connection is that not all types of three-phase connections are possible. For example, the ∆-Y and Y- ∆ connections are not possible using the autotransformer.
The Y-Y connection must share a common neutral between the high-voltage and low-voltage windings, so the neutrals of the circuits connected to these windings cannot be isolated.
A ∆ – ∆ autotransformer connection is theoretically possible; however, this will create a peculiar phase shift. The phase shift is a function of the ratio of the primary to secondary voltages and it can be calculated from the vector diagram.
This phase shift cannot be changed or eliminated and for this reason, autotransformers are very seldom connected as ∆ – ∆ transformers.
1.5 ADVANTAGES OF THE AUTOTRANSFORMER
- There are considerable savings in size and weight.
- There are decreased losses for a given KVA capacity.
- Using an autotransformer connection provides an opportunity for achieving lower series impedances and better regulation. Its efficiency is more when compared with the conventional one.
- Its size is relatively very smaller.
- Voltage regulation of autotransformer is much better.
- Lower cost
- Low requirements of excitation current.
- Less copper is used in its design and construction.
- In conventional transformer the voltage step up or step down value is fixed while in autotransformer, we can vary the output voltage as per out requirements and can smoothly increase or decrease its value as per our requirement.
1.6 DISADVANTAGES OF THE AUTOTRANSFORMER
- The autotransformer connection is not available with certain three-phase connections.
- Higher (and possibly more damaging) short-circuit currents can result from a lower series impedance.
- Short circuits can impress voltages significantly higher than operating voltages across the windings of an autotransformer.
- For the same voltage surge at the line terminals, the impressed and induced voltages are greater for an autotransformer than for a two-winding transformer.
- Autotransformer consists of a single winding around an iron core, which creates a change in voltage from one end to the other. In other words, the self-inductance of the winding around the core changes the voltage potential, but there is no isolation of the high and low voltage ends of the winding. So any noise or other voltage anomaly coming in on one side is passed through to the other. For that reason, Autotransformers are typically only used where there is already some sort of filtering or conditioning ahead of it, as in electronic applications, or the downstream device is unaffected by those anomalies, such as an AC motor during starting.
CHAPTER FIVE
5.1 CONCLUSION
Seeing as how we can tap any transformer winding to obtain the equivalent of several windings (albeit with loss of electrical isolation between them), it makes sense that it should be possible to forego electrical isolation altogether and build a transformer from a single winding. Indeed this is possible, and the resulting device is called an autotransformer
Autotransformers find popular use in applications requiring a slight boost or reduction in voltage to a load. The alternative with a normal (isolated) transformer would be to either have just the right primary/secondary winding ratio made for the job or use a step-down configuration with the secondary winding connected in series-aiding (“boosting”) or series-opposing (“bucking”) fashion. Primary, secondary, and load voltages are given to illustrate how this would work.
5.2 RECOMMENDATION
This project is designed to be used in homes and industries and wherever the need for power distribution and consumption is needed. And should be used and maintain by a qualified personnel.
CHAPTER TWO: The chapter one of this work has been displayed above. The complete chapter two of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" is also available. Order full work to download. Chapter two of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" consists of the literature review. In this chapter all the related work on "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" was reviewed.
CHAPTER THREE: The complete chapter three of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" is available. Order full work to download. Chapter three of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" consists of the methodology. In this chapter all the method used in carrying out this work was discussed.
CHAPTER FOUR: The complete chapter four of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" is available. Order full work to download. Chapter four of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" consists of all the test conducted during the work and the result gotten after the whole work
CHAPTER FIVE: The complete chapter five of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" is available. Order full work to download. Chapter five of "design and construction of a three phase auto-transformer of rating 2.5kva, and step down voltage of 415 and secondary taps of 0.,180v, 200v, 230v and 240v" consist of conclusion, recommendation and references.
To "DOWNLOAD" the complete material on this particular topic above click "HERE"
Do you want our Bank Accounts? please click HERE
To view other related topics click HERE
To "SUMMIT" new topic(s), develop a new topic OR you did not see your topic on our site but want to confirm the availiability of your topic click HERE
Do you want us to research your new topic? if yes, click "HERE"
Do you have any question concerning our post/services? click HERE for answers to your questions
For more information contact us through any of the following means:
Mobile No :+2348146561114 or +2347015391124 [Mr. Innocent]
Email address :engr4project@gmail.com
COUNTRIES THAT FOUND OUR SERVICES USEFUL
Australia, Botswana, Canada, Europe, Ghana, Ireland, India, Kenya, Liberia, Malaysia, Namibia, New Zealand, Nigeria, Pakistan, Philippines, Singapore, Sierra Leone, South Africa, Uganda, United States, United Kindom, Zambia, Zimbabwe, etc
Support: +234 8146561114 or +2347015391124
Watsapp No :+2348146561114
Email Address :engr4project@gmail.com
FOLLOW / VISIT US VIA: