phonelogo+234 8146561114 or +2347015391124
PROTECTION OF DISTRIBUTION TRANSFORMER ARISING FROM OVER- VOLTAGE

USER'S INSTRUCTIONS: The project work you are about to view is on "protection of distribution transformer arising from over- voltage". Please, sit back and study the below research material carefully. This project topic (protection of distribution transformer arising from over- voltage) have complete 5(five) Chapters. The complete Project Material/writeup include: Abstract + Introduction + etc + Literature Review + methodology + etc + Conclusion + Recommendation + References/Bibliography.Our aim of providing this "protection of distribution transformer arising from over- voltage" project research material is to reduce the stress of moving from one school library to another all in the name of searching for "protection of distribution transformer arising from over- voltage" research materials. We are not encouraging any form of plagiarism. This service is legal because, all institutions permit their students to read previous projects, books, articles or papers while developing their own works.


TITLE PAGE

PROTECTION OF DISTRIBUTION TRANSFORMER ARISING FROM OVER- VOLTAGE

BY

---
EE/H2013/01430
DEPARTMENT OF ----
SCHOOL OF ---
INSTITUTE OF ---

DECEMBER,2018



APPROVAL PAGE

This is to certify that the research work, "protection of distribution transformer arising from over- voltage" by ---, Reg. No. EE/H2007/01430 submitted in partial fulfillment of the requirement award of a Higher National Diploma on --- has been approved.

By
---                                                     . ---
Supervisor                                                  Head of Department.
Signature……………….                           Signature……………….        

……………………………….
---
External Invigilator



DEDICATION
This project is dedicated to Almighty God for his protection, kindness, strength over my life throughout the period and also to my --- for his financial support and moral care towards me.Also to my mentor --- for her academic advice she often gives to me. May Almighty God shield them from the peril of this world and bless their entire endeavour Amen.



ACKNOWLEDGEMENT

The successful completion of this project work could not have been a reality without the encouragement of my --- and other people. My immensely appreciation goes to my humble and able supervisor mr. --- for his kindness in supervising this project.
My warmest gratitude goes to my parents for their moral, spiritual and financial support throughout my study in this institution.
My appreciation goes to some of my lecturers among whom are Mr. ---, and Dr. ---. I also recognize the support of some of the staff of --- among whom are: The General Manager, Deputy General manager, the internal Auditor Mr. --- and the ---. Finally, my appreciation goes to my elder sister ---, my lovely friends mercy ---, ---, --- and many others who were quite helpful.


PROJECT DESCRIPTION: This work "protection of distribution transformer arising from over- voltage" research material is a complete and well researched project material strictly for academic purposes, which has been approved by different Lecturers from different higher institutions. We made Preliminary pages, Abstract and Chapter one of "protection of distribution transformer arising from over- voltage" visible for everyone, then the complete material on "protection of distribution transformer arising from over- voltage" is to be ordered for. Happy viewing!!!


ABSTRACT

Increase in voltage for the very short time in power system is called as the over voltage. The voltage stress caused by over voltage can damage the lines and equipment’s connected to the system. There are two types of causes of over voltage in power system – over voltage due to external causes and over voltage due to internal causes. Over voltages can be generated at high frequency (load switching and lightning), medium frequency (capacitor energizing), or low frequency. Over-voltage due to external causes:
This cause of over voltage in power system is the lightning strokes in the cloud. By considering direct lightning strokes to a connected overhead distribution line, the effectiveness of the common practice transformer protection scheme and of an alternative one utilizing shorter surge arrester connection conductors in suppressing fast-front over-voltages was evaluated. A shorter length of the surge arrester connection conductors results in a reduction in the amplitude of the over-voltages arising at the medium-voltage terminals of the transformer and in a slower rate of increase of the overvoltage amplitude with lightning return-stroke current. The over-voltages transferred to the low-voltage terminals of the transformer are practically not affected by the length of the surge arrester connection conductors. Protection against transferred over-voltages was provided by surge protective devices installed at the low-voltage terminals of the transformer. By utilizing shorter surge arrester connection conductors the transformer failure rate, estimated through risk assessment, is reduced by approximately 11%.


TABLE OF CONTENTS
COVER PAGE
TITLE PAGE
APPROVAL PAGE
DEDICATION
ACKNOWELDGEMENT
ABSTRACT
CHAPTER ONE
1.0      INTRODUCTION

    1. BACKGROUND OF THE PROJECT
    2. PROBLEM STATEMENT
    3. AIM OF THE PROJECT
    4. OBJECTIVE OF THE PROJECT
    5. SIGNIFICANCE OF THE PROJECT
    6. SCOPE OF THE PROJECT
    7. PROJECT ORGANISATION

CHAPTER TWO
LITERATURE REVIEW

    1. OVERVIEW OF DISTRIBUTION TRANSFORMER
    2. TYPES OF DESTRIBUTION TRANSFORMER
    3. USE OF DESTRIBUTION TRANSFORMER
    4. STRESS FACTORS AND PROTECTION METHODS
    5. CAUSES OF OVER VOLTAGE IN POWER SYSTEM
    6. EFFECTS OF OVER VOLTAGES ON POWER SYSTEMS
    7. REVIEW OF OVERVOLTAGE PROTECTION
    8. METHODS OF PROTECTION AGAINST LIGHTNING
    9. INSULATION COORDINATION

CHAPTER THREE
METHODOLOGY

    1. MODELLING OF THE EVALUATED SYSTEM

CHAPTER FOUR
4.0      RESULT ANALYSIS

    1. SIMULATION RESULTS AND DISCUSSION
    2. RISK ASSESSMENT

CHAPTER FIVE

    1. CONCLUSION

REFERENCES

 

 

CHAPTER ONE

1.0                                                              INTRODUCTION

1.1                                                 BACKGROUND OF THE STUDY

The fast-front over-voltages arising at distribution equipment utilizing non-self-restoring insulation, such as transformers or cables, may cause permanent failure resulting in system outages and economic losses. Therefore, distribution equipment is most commonly protected against impinging lightning surges by surge arresters and surge protective devices. It is well known that the efficiency of the afforded protection is affected by the length of the connection conductors; the latter should be as short as possible in order to achieve optimum protection [1-6].
According to common practice, distribution transformers are protected against impinging lightning surges by surge arresters installed close to their medium-voltage bushings. It can be shown theoretically that the fast-front over-voltages arising at a protected transformer increase in amplitude with the steepness of the incoming lightning surge and that the greater the separation distance between surge arresters and transformer the less is the effectiveness of the provided protection. Actually, analytical methods for the estimation of the lightning over-voltages arising at a protected transformer can be found in [7, 8]. However, as theoretical analysis is based on several simplifications, analytical results should be considered as conservative yet acceptable estimates for the protective distance and the safety margin provided by surge arresters. A more accurate evaluation of the protection afforded by surge arresters to the transformer can be made with the aid of detailed simulations using an electromagnetic transient analysis program.
In this study the effects of the length of the surge arrester connection conductors on the fast-front over-voltages arising at a typical pole-mounted 50 kVA, 20/0.4 kV transformer of the Hellenic distribution system are investigated through detailed ATP-EMTP [9] simulations. By considering both first and subsequent direct lightning strokes to the connected medium-voltage overhead line, the common practice transformer protection scheme and an alternative one utilizing shorter surge arrester connection conductors were evaluated. A better lightning performance of the transformer is achieved by implementing the alternative than the common practice protection scheme; the transformer failure rate, estimated through risk assessment, is reduced which is the aim of this study.

1.2                                                       PROBLEM STATEMENT
The most cause of damages in the lines and equipments connected to the system is caused by over-voltage coming from the distribution transformer. In other to solve these problem researchers came out the solution of protection to the distribution transformer. This protection against transferred over-voltages was provided by surge protective devices installed at the transformer. It is done by utilizing shorter surge arrester connection conductors the transformer failure rate, estimated through risk assessment, is reduced.

1.3                                                          AIM OF THE PROJECT
The main aim of this work is to use a shorter length of the surge arrester connection conductors results in a reduction in the amplitude of the over-voltages arising at the medium-voltage terminals of the transformer and in a slower rate of increase of the overvoltage amplitude with lightning return-stroke current.

1.4                                                   OBJECTIVES OF THE PROJECT
At the end of the study, the effectiveness of the common practice transformer protection scheme and of an alternative one utilizing shorter surge arrester connection conductors in suppressing fast-front over-voltages shall be evaluated.
Protection against transferred over-voltages was provided by surge protective devices installed at the low-voltage terminals of the transformer. By utilizing shorter surge arrester connection conductors the transformer failure rate, estimated through risk assessment, is reduced by approximately 11%.

1.5                                               SIGNIFICANCE OF THE PPROJECT
Many kinds of transformers can be found in the market which includes two winding power transformers, three windings power transformers, auto transformers, regulating transformers, earthing transformers.
Depending on the use of the transformer, winding connections, earthing methods, mode of operation and other various factors, decision on the kind of protection that should be used for the transformer is made. Considering the type of protection will help the transformer to last long and be safe to use.

1.6                                                        SCOPE OF THE PROJECT
In this study, the effects of the length of the surge arrester connection conductors on the lightning surges impinging on a typical wood pole-mounted 50 kVA, 20/0.4 kV transformer of the Hellenic distribution system are investigated through detailed ATP-EMTP simulations. By considering both first and subsequent direct lightning strokes to a connected overhead distribution line, the effectiveness of the common practice transformer protection scheme and of an alternative one utilizing shorter surge arrester connection conductors in suppressing fast-front over-voltages was evaluated. A shorter length of the surge arrester connection conductors results in a reduction in the amplitude of the over-voltages arising at the medium-voltage terminals of the transformer and in a slower rate of increase of the overvoltage amplitude with lightning return-stroke current.

1.7                                                         PROJECT ORGANISATION

The work is organized as follows: chapter one discuses the introductory part of the work, chapter two presents the literature review of the study,  chapter three describes the methods applied, chapter four discusses the results of the work, chapter five summarizes the research outcomes and the recommendations.

CHAPTER TWO: The chapter one of this work has been displayed above. The complete chapter two of "protection of distribution transformer arising from over- voltage" is also available. Order full work to download. Chapter two of "protection of distribution transformer arising from over- voltage" consists of the literature review. In this chapter all the related work on "protection of distribution transformer arising from over- voltage" was reviewed.

CHAPTER THREE: The complete chapter three of "protection of distribution transformer arising from over- voltage" is available. Order full work to download. Chapter three of "protection of distribution transformer arising from over- voltage" consists of the methodology. In this chapter all the method used in carrying out this work was discussed.

CHAPTER FOUR: The complete chapter four of "protection of distribution transformer arising from over- voltage" is available. Order full work to download. Chapter four of "protection of distribution transformer arising from over- voltage" consists of all the test conducted during the work and the result gotten after the whole work

CHAPTER FIVE: The complete chapter five of design and construction of a "protection of distribution transformer arising from over- voltage" is available. Order full work to download. Chapter five of "comparative analysis of bitter kola, moringa oleifera seed, and wonderful kola used for waste water treatment" consist of conclusion, recommendation and references.

CLICK HERE FOR MORE RELATED TOPICS/MATERIAL


To "DOWNLOAD" the complete material on this particular topic above click "HERE"

Do you want our Bank Accounts? please click HERE

To view other related topics click HERE

To "SUMMIT" new topic(s), develop a new topic OR you did not see your topic on our site but want to confirm the availiability of your topic click HERE

Do you want us to research your new topic? if yes, click "HERE"

Do you have any question concerning our post/services? click HERE for answers to your questions


For more information contact us through any of the following means:

Mobile No: +2348146561114 or +2347015391124 [Mr. Innocent]

Email address: engr4project@gmail.com

Watsapp No: +2348146561114


COUNTRIES THAT FOUND OUR SERVICES USEFUL

Australia, Botswana, Canada, Europe, Ghana, Ireland, India, Kenya, Liberia, Malaysia, Namibia, New Zealand, Nigeria, Pakistan, Philippines, Singapore, Sierra Leone, South Africa, Uganda, United States, United Kindom, Zambia, Zimbabwe, etc
Support: +234 8146561114 or +2347015391124

Watsapp No
: +2348146561114


E
mail Address: engr4project@gmail.com


FOLLOW / VISIT US VIA:

tweeter instagram.htmlfacebook logo